Abstract
In Korea, water supply and drainage noises result in one of the main noise complaints because more than 50% of people reside in multi-residential buildings. In this study, a series of field measurements were therefore carried out to examine the current noise situation. The noise levels were measured in the bathrooms of the upper and lower floors, as well as in habitable rooms. The measurement results for the bathrooms of the lower floor (N = 113) are 47.8 dBA (water closet), 42.7 dBA (basin), and 33.9 dBA (bathtub) for water drainage, while values vary between 33.7 dBA and 37.0 dBA for the water supply. The results suggest that the water drainage noise needs to be controlled first. The system bathroom (42.8 dBA) produced lower noise levels than the wet construction method (48.2 dBA) for all of the sanitary wares. The highest noise levels in the living rooms (N = 11) and bedrooms (N = 8) of the lower floor are 34.3 dBA and 39.1 dBA, respectively. The average noise level in the rooms (N = 19) is 37.8 dBA. The overall result suggests that it is necessary to develop an acoustic guideline to satisfy the higher Class of the 2nd ISO/CD 19488, although the current noise level satisfies Class C (living room) and Class D (bedroom).
Original language | English |
---|---|
Article number | 372 |
Journal | Applied Sciences (Switzerland) |
Volume | 6 |
Issue number | 11 |
DOIs | |
State | Published - 22 Nov 2016 |
Keywords
- Bathroom
- Field measurement
- Multi-residential building
- Water supply and drainage noise